Introduction and working principle of condenser rubber ball online cleaning device

Introduction and working principle of condenser rubber ball online cleaning device

Overview of condenser rubber ball online cleaning installation

The condenser rubber ball online cleaning device is a device for effectively cleaning the condenser cooling pipe during the operation of the air conditioning unit. The installation performance of the equipment directly affects the cleaning level and heat transfer effect of the condenser. The scope of application of this installation is quite common. It is not only suitable for the cleaning of air-conditioning condensers, but also for petroleum, petrochemical, chemical, and iron and steel units; cleaning of cooling pipes of fixed tube-plate heat exchangers and cleaning of air-conditioning evaporators. Peide brand The condenser rubber ball on-line cleaning device can be put into use at any time under continuous working conditions without reducing the load, so that the cooling pipe is in a relatively clean state, the service life of expensive equipment is maximized, and manual pass guns are greatly reduced, saving 8-15% Of energy. It is an indispensable cleaning device for the safe and economic operation of condensers and heat exchangers in petroleum, chemical, steel and other enterprises and buildings.

Working principle of condenser rubber ball online cleaning installation

The condenser rubber ball online cleaning device selects a suitable rubber ball, and puts the rubber ball into the tee from the hole of the loading hand, and the number of balls is about 30% of the number of cooling water pipes. First make sure that the rubber ball is all below the water surface, then open the deflated air on the top of the teeing room, close the exhaust valve, and then open the pump exhaust valve to close the air exhaust, and then press the cleaning button. Driven by the water flow, it enters the condenser water chamber. The rubber ball is washed and cooled under the pressure difference between the inlet and outlet of the circulating water

Wipe inside the cooling pipe to make the dirt on the inner wall of the cooling pipe come out with the water flow. The rubber ball is driven into the ball collector by the circulating water. The rubber ball is separated by the ball net and pumped by the rubber ball pump. The incoming water flow is sucked into the teeing room, and the water pipe is continuously cleaned. Generally, the new system can clean the air-conditioning condenser and evaporator 1 to 2 times a day, and the old system can be cleaned multiple times.